1-1171. Specifications7-24. Diagnosis TableWired remoteCauseE 0 1E 0 2E 0 9E 1 4E 0 4E 0 6E 1 5E 1 6E 2 0P 0 5L 0 2P 0 9 displayedL 0 7 displayedIndoor unit1:1 connection (single type)Nothing isdisplayedNothing isdisplayeddisplayeddisplayed Operating lampis blinking.displayeddisplayeddisplayeddisplayeddisplayeddisplayeddisplayeddisplayeddisplayeddisplayedL 1 3Standby lampis blinking.Operation lamp andStandby lamp areblinking alternately.Both the Operationlamp and Standbylamp are blinkingtogether.Timer lamp andStandby lamp areblinking alternately.Remote controller is not connected correctly.Indoor unit power is not ON.Automatic address setting has not beencompleted.Inter-unit control wiring is cut or is notconnected correctly.Remote controller is not connected correctly(remote controller receiving failure).Remote controller is not connected correctly(failure in transmission from remote controllerto indoor unit).Indoor-outdoor inter-unit wiring is notconnected correctly.Indoor unit capacity is too low.Indoor unit capacity is too high.No serial signal is being received at all fromthe indoor units.Inter-unit circuit or open phase in the outdoorunit powerInsufficient gasIndoor-outdoor unit type mismatchThe indoor unit ceiling panel connector is notconnected correctly.Group connectionRemote controller is not connected withindoor unit correctlyIndoor unit power is not ON.Automatic address setting has not beencompleted.Inter-unit control wiring is cut or is notconnected correctly.Remote controller is not connected withindoor unit correctlyRemote controller is not connected withindoor unit correctlySame as at leftIndoor-outdoor inter-unit wiring is cut oris not connected correctly.Same as at leftReversed phase or open phase in the3-phase power at one of the outdoorunits in the groupSame as at leftCeiling panel connector at one of theindoor units in the group is notconnected correctly.Simultaneous-operation multi system(flexible combination)Same as at leftSame as at leftSame as at leftControl wiring for group control is cut oris not connected correctly.Same as at leftSame as at leftSame as at leftReversed phase or open phase in theoutdoor unit 3-phase powerSame as at leftControl wiring for group control is connectedto the indoor unit, however it is set for individualoperation.Indoor unit ceiling panel connector is notconnected correctly.Control by main-subremote controllersSame as at leftSame as at leftSame as at left2 remote controllers areset as the main remotecontroller.Same as at leftSame as at leftSame as at leftSame as at leftSame as at leftSame as at leftSame as at leftreceiver lampspcontroller dilay1