FP2 Analog UnitInitial Settings5 - 65.2 Analog Output Initial Settings5.2 Analog Output Initial SettingsPerforms the initial settings for each channel of the analog output. The initial settings areset by sequence program at the first scan at the start of operation. (The initial settingsfor the analog unit are enabled only for one time after operation start.)The items for the initial settings are given below.D Analog output hold setting (when you do not want to clear theanalog output in the PROG. mode)D Analog output hold (any value) data setting (when you want tohold at a desired value in the PROG. mode)5.2.1 Analog Output Hold SettingSpecifies either non - hold, hold (final value during RUN mode), or hold (any value)operation for each output channel. (Default is non - hold operation.)5.2.2 Analog Output Hold (any value) Data SettingSpecifies the digital data for the analog output that you want to output at the outputchannel set at “hold (any value)” in the analog output hold setting.The data that can be specified is as shown below for each range.- ±10V range: K - 2048 to K2047- 0 to 20mA: K0 to K4095Program example:When you want to hold a 10mA output at ch0 in the program mode.R9013F151 WRT , K 0 , DT 0 , K 2 , K 38Shared memory address 38 is head addressDT0 = H0002DT1 = K2047When the analog outputunit is installed at slot 0Initial settingPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com