FP2 Analog Unit Initial Settings5 - 55.1 Analog Input Initial Settings5.1.4 Analog Input Offset Changing SettingSpecifies the digital value for the offset amount for each input channel.Between the range K - 2048 to K2047 can be set as the digital value for the offset amount;however, the range that can be obtained for the analog input conversion value that theoffset is applied to is limited to between K - 32768 and K32767.Program example:When the applied offsets are ch0: K0 (no offset), ch1: K3, ch2: K10, and ch3: K20R9013 F151 WRT, K0 , DT 0 , K4 , K30Shared memory address 30 is head addressDT0 = K0DT1 = K3DT2 = K10DT3 = K20When the analog inputunit is installed at slot 0Initial settingPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com