2211.2.3. Range and settings of thermal protection / nominal intensity of the contactors (class AC3)Models 140 150 170 190 210FTI Range 24-32A 23-32A 30-40A 30-40A 37-50AAdjustment 32A 32A 38A 38A 46AFT2 Range 20-25A 23-32A 23-32A 30-40A 30-40AAdjustment 22A 27A 32A 32A 32AFT3 Range 24-32A 23-32A 23-32A 30-40A 37-50AAdjustment 32A 32A 32A 38A 46AFT4 Range 20-25A 23-32A 23-32A 30-40A 30-40AAdjustment 22A 27A 27A 32A 32AFTOF1-L Range 2,5-4A 2,5-4A 6-10A 6-10A 6-10AAdjustment 3,5A 3,5A 7A 7A 7AFTOF1-H Range 2,5-4A 2,5-4A 6-10A 6-10A 6-10AAdjustment 3,5A 3,5A 7A 7A 7AFTOF2-L Range 2,5-4A 2,5-4A 2,5-4A 6-10A 6-10AAdjustment 3,5A 3,5A 3,5A 7A 7AFTOF2-H Range 2,5-4A 2,5-4A 2,5-4A 6-10A 6-10AAdjustment 3,5A 3,5A 3,5A 7A 7AFTWPStandard pumpRange 6-10A 6-10A 6-10A 6-10A 6-10AAdjustment 6,4A 6,4A 6,4A 6,4A 6,4AFTWPHigh pressure pumpRange 9-14A 9-14A 9-14A 9-14A 9-14AAdjustment 10,5A 10,5A 10,5A 10,5A 10,5AContactorsKOF1 / KOF1-L / KOF1-H 6A 6A 9A 9A 9AKOF2 / KOF2-L / KOF2-H 6A 6A 6A 9A 9AKWP1/2 Standard pump 9A 9A 9A 9A 9AKWP1/2 High pressure pump 12A 12A 12A 12A 12A