1 27. 01. 17. Leaflet Number 671372IntroductionThe NALT-H unit is supplied with a pre-wired terminal boxand an IP44 rated, class B insulated motor. The fans aredesigned to convey clean air with a maximum temperatureup to 60 Deg.C (40 Deg.C - model NALT-315-H).Do not operate the fan in the presence of inflammable vapours(alcohol etc).An adequate supply of fresh air must be provided if the fan is tobe fitted in a room with a gas burning appliance which is not ofthe balance flue type.1.0 HandlingAlways handle the fans carefully to avoid damage anddistortion. Care should be taken to ensure that any slings usedfor lifting purposes do not damage the casing, connection box,impeller or inlet cone.2.0 InstallationInstallation must be carried out by a competent person inaccordance with the appropriate authority and conforming to allstatutory and governing regulations i.e. IEE, CIBSE, COSHE etc.From the fan rating plate, observe the weight of the unit andselect the mounting position and structure that can supportthe unit.These fans are not for stand-alone use. They are designed to beincorporated into ducted systems, machines or where safeoperation has been ensured by providing applicable protectionto moving parts.This unit is not designed for external use. Before installingensure the impeller is running freely and there are noobstructions to the airflow.A robust mounting foot is available as an accessory, to easeinstallation.3.0 Dimensions (mm) & Weights (kg)Code A B C D Weight(Kg)NALT-100H 194 23 243 98 3NALT-125H 195 27 243 123 3NALT-150H 214 24 333 147 5NALT-200H 223 25 333 198 5NALT-250H 206 27 333 248 6NALT-315H 230 25 401 312 84.0 Technical DataCode Nom Max Max Max Sound Maxspeed adsorbed adsorbed air volume pressure temppower current (m 3/s) level (oC)(W) (A) dbA @3mNALT-100H 2500 78 0.33 0.077 47 60NALT-125H 2450 80 0.35 0.12 47 60NALT-150H 2700 120 0.53 0.19 50 60NALT-200H 2600 170 0.72 0.27 52 60NALT-250H 2750 180 0.80 0.31 54 60NALT-315H 2700 350 1.45 0.52 55 50Isolation - Before commencing work make surethat the unit, and any control areelectrically isolated from the mains supply.ABD CBFig. 2.Code descriptions1. Centrifugal Tube Fan Range2. Case Size3. H = High PerformanceNALT - 100H| | |1 2 3Fig. 1.The EMC Directive2014/30/EUThe Low Voltagedirective2014/35/EUNALT-H FANSMetal Cased Centrifugal FansInstallation and MaintenanceNuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NAT: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk