X GEM-P1632 Programming Instructions L NAPCO Security Systems! Page 4SYSTEM PROGRAMMING OPTIONSINTRODUCTIONThe GEM-P1632 control panel may be programmed by various means, each of which will be covered in detail in thesections that follow. Keypad displays shown are for a GEM-K2AS, GEM-K3DGTL and GEM-K4RF series keypads. Withthe GEM-RP2ASe2 and GEM-K2AS keypads, because of their reduced display capabilities, messages are abbreviatedand will scroll through two or more screens. Zone descriptions cannot be programmed using GEM-K2AS or GEM-RP2ASe2 keypad, therefore a GEM-RP1CAe2/GEM-K1CA must be used (see WI897).! Downloading From a Computer. This is the preferred method of programming. The panel may be downloadedfrom (or uploaded to) an IBM PC-compatible computer, either locally or remotely. Napco's PCD-WindowsQuickloader software features context-sensitive help screens as well as an error-checking utility that preventsprogramming of incompatible or conflicting data to ensure proper panel operation. Note: Unattended download-ing from a computer is not allowed for Fire Alarm or UL installations.! Easy Menu-Driven Program (Dealer Program) Mode - Keypad Programming. The Easy Menu-DrivenProgram Mode allows keypad programming of number of zones in area 1, panel zone doubling, number of firezones (both 4-wire and 2-wire), local or Central Station reporting, number of exit/entry zones, number of interiorzones, number of 24 hour zones, number of chime zones, Chime 2 zones, Exit/Entry2 zones, 50ms loop responsezones (Note: 750mS is required for Loop Response time in UL installations) , aux output activated on alarm zones,sensor watch zones, keypad sounder on alarm zones, auto bypass re-entry zones, EOLR zones, number of key-pads in area 1, Central Station telephone number, Central Station account number, Central Station receiver for-mat, User Codes, RF transmitter points, RF keyfob transmitters, zone descriptions, dealer code, Telco line faulttest, Burg output chirp on keyfob, enable CP-01, and clear dealer program/cold start. For new panels, a customdefault program may be created at the keypad. A menu-driven utility prompts the installer to configure the system.Further detailed customization is accomplished in the Direct Address Program Mode.! Direct Address (Dealer Program) Program Mode - Keypad Programming. The Direct Address Program Modeis an extension of the Dealer Program Mode wherein data is entered at the keypad by specific location. This modeis accessed from the Easy Menu Driven Program Mode by pressing the C button at any time.! User Program Mode - Keypad programming. The User Program Mode is intended forauthorized users and is limited to keypad programming of User Codes, Time, Date and ZoneDescriptions.DOWNLOADING FROM A COMPUTERThe control-panel program may be downloaded from the computer by any of the following methods.Local Downloading(Note: This procedure should be used after installation, after peripheral devices are connected).For direct high-speed data transfer to the control panel from a desktop computer, connect the download jack (JP2)on the panel to the LOCAL jack (J3) on the Napco PCI2000/3000 computer interface using the supplied 6-conductor cable. (Refer to PCI2000/3000 Installation Instructions WI443 for wiring diagram and procedures).Similarly, a high-speed local download may be made in the field using a notebook or laptop computer. ConnectJP2 on the control panel to a Napco PCI-MINI computer interface using the 6-conductor cable supplied. (Refer toPCI-MINI Installation Instructions WI767).Remote Downloading(Also see PCI2000/3000 Installation Instructions WI443). Note: Unattended downloading from a computer is notallowed for Fire Alarm or UL installations.Function Mode.Start by establishing a telco connection between the computer operator and the installer. During this procedure,voice contact will be lost, therefore both the installer and the computer operator should be familiar with theoperation. When a steady high-pitched tone is heard at the site phone, access the ìACTIVATE DOWNLOADî Function(see Keypad Programming Modes), then press the U button or the YES button; the site phone will go dead. Hangup the phone and wait for a call from the central station confirming a successful download.Callback Method.An installed, unattended panel may be programmed or reprogrammed remotely using the Callback-MethodDownload feature of the PCD Windows software. Remote downloading requires a modem compatible with thePCI2000/3000. Upon answering the call from the computer, the panel will verify the Download Security Code and,if confirmed, will establish a connection. If a Callback Number is programmed into the panel, the panel willautomatically disconnect and call the computer at this number before establishing a connection.System Programming Options