Technical Information >User GuideG50AInitial SettingsWhen the G50A is powered for the first time selectgroup setting option 4 (press 4), after the initialisationhas finished.If system is already working Press “ ” curser keystogether for 3 sec until the second menu appears.Select group setting option 1 (press “1”).Select the group to change with the group select switch.Enter the indoor addresses (001 enter, 002 enter etc)in that group.To enter the remote controller address press “ ”key until the curser is underneath “remote controller”and enter the remote controller address.If you want to name the group press “ ” until groupname set is flashing, then press enter.Use the curser keys to highlight the letter requiredand press enter.When the name is complete press the back screenbutton to return to the group screen.Try to make the group number the same as firstaddress in that group.When all groups are complete, press back screento return to the menu. Press “ ” curser keystogether for 3 sec to return to the user menu.Timer SettingPress the back screen until the user menu is displayed.Select option 3 schedule setting (press 3).Use the curser keys to select the timer patternP1, P2, P3 or P4 then press enter.Use the clock pattern buttons to set the On time.Move the curser and set the Off time.Once all the on/off ’s have been set press the backscreen to return to the previous screen.Move the curser under the day of the week youwant to apply the pattern to and with clock patternbuttons set the pattern number.If you want to apply the same timer patterns to eachgroup move the curser to M in the bottom right of thescreen and press enter to put the settings into memorychange the group with the group setting button anduse MR enter to put the timer settings into that group.When this is complete back screen to the menu andthe timer is set.Back Screen ButtonRepeated pressing of the back screen button willreturn to a menu screen.4/Temp5/Clock Pattern6/Air DirectionBack Screen7/Temp8/Clock Pattern9/Ventilation1/On/Off 2/Mode 3/Fan Speed Group Select0/Remote Prohibit Timer Mode Del/Reset Curser Keys Enterwww.mitsubishielectric.co.uk/aircon