Appendix A. Specifications11 kVA UPS unitsOverview - 11 kVA UPS unitsSpecification RT11kVA 6U Rack or TowerUPS (200-240VAC)RT11kVA 6U 3:1 Phase Rackor Tower UPS (380-415VAC)GeneralPart Number 5594-9KX5594-RU8, FC A5445594-9PX5594-RU8, FC A547Country World WideForm factor 6 U Rack or TowerTopology Online, double conversion, sine wave outputHE (High Efficiency) mode: Line interactiveEBM Support Yes (55949BX) Yes (55949BX)EPOW connector Yes YesMBP Required Yes, single phase Yes, three phaseNetwork Management Card Yes, shipped with UPS in thebox, needs to be installedYes, shipped with UPS in thebox, needs to be installedVA/Watts rating 11000 VA10000 W11000 VA10000 WEfficiency (on utility power) Online mode: Up to 94.5%High efficiency mode: Up to 98%Transfer time Online mode: 0 ms (no break)High efficiency mode: 10 ms maximum (due to loss of utilitypower)Leakage current Leakage current of the equipment is up to 5% of input current forthe leakage current defined by the Input ground to UPS chassisper the UL standard 60950 5.1 Touch current and protectiveconductor current.For additional information see the section Leak current informationin Chapter 12.Energy Star compliant Yes No6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG 255