3232A0.03 Set the operatingfrequency in digital modeRange: Lower limit offrequency ~upper limitof frequency【50.00Hz】When the main reference frequency is set in digitalmode(A0.02 = 0), this setting of A0.03 is the drive’sinitial frequency value.A0.04 Methods of inputtingoperating commands 0~2【0】FV100 has two control modes.0: Panel control:Input operating commands via panelStart and stop the drive by pressing RUN, STOP and Mon the panel.1: Terminal control: Input operating commands viaterminals.Use external terminals Xi(Set function codeA6.00~A6.06 to 1 and 2),M Forward, M Reverse to startand stop the drive.2:Modbus communication.A0.05 Set running direction 0~1【0】This function is active in panel control mode , andinactive in terminal control mode.0: Forward1: ReverseA0.06 Acc time 1 0.0~6000.0s【6.0s】A0.07 Dec time 1 0.0~6000.0s【6.0s】Default value of Acc/Dec time 1:2kW or below:6.0S30kW~45kW:20.0S45kW or above:30.0SAcc time is the time taken for the motor to acceleratefrom 0Hz to the maximum frequency (as set in A0.08).Dec time is the time taken for the motor to deceleratefrom maximum frequency (A0.08) to 0Hz.FV100 series VFD has defined 4 kinds of Acc/Dectime.(Here only Acc/Dec time 1 is defined, and Acc/Dectime 2~4 will be defined in A4.01~A4.06),and theAcc/Dec time 1~4 can be selected via the combinationof multiple function input terminals,please refer toA6.00~A6.07.A0.08 Max. outputFrequencyMax{50.00,A0.11 upper limit offrequency}~300.00Hz【50.00】A0.09 Max. outputVoltage 0~480V【VFD’s rating values】A0.10 Upper limitof frequency A0.11~A0.08【50.00】A0.11 Lower limitof frequency 0.00~A0.10【00.00】A0.12 Basicoperating frequency 0.00~300【50.00】Max output frequency is the highest permissible outputfrequency of the drive, as shown in Fig. 6-1 as Fmax;Max output voltage is the highest permissible outputvoltage of the drive, as shown in Fig. 6-1 as VmaxUpper limit of frequency is the highest permissibleoperating frequency of the user setting, as shown in Fig.6-1 as FH.Lower limit of frequency is the lowest permissibleoperating frequency of the user setting,as shown inFig.6-1 as FL.Basic operating frequency is the Min. frequency whenthe drive outputs the max voltage in V/F mode, as shownin Fig. 6-1 as FbFL FH Fb FmaxVmaxOutputVoltageOutput frequencyFig.6-1 Characteristic parameters