Page 46 Operating Instructions Powador-proLOG_EN10 UpdateKACO new energy cannot assume any liability or repair costsfor damage resulting from a failure to observe these instruc-tions. Please do not make changes to any directories or filesother than the ones described.10.1 Update with card reader10.1.1 General informationA Compact Flash (CF) card is built into the Powador-proLOG.The entire operating system for the Powador-proLOG and allthe system files are stored on this card. You will find the cardslot on the right-hand side of the housing.10.1.2 InstructionsTo perform the update, you will need a Powador-proLOG, acard reader for CF cards, a PC or laptop and the new software(which you can obtain via the monitoring service).Section 10 · UpdateDANGERBefore starting the update, make sure to disconnect thepower plug for the data logger. The Powador-proLOGmust be switched off when removing the card from thedata logger.NOTEAfter the update, the unit will need to be reconfiguredusing the installation wizard.ACTION– Remove the protective cover from the card slot and takeout the CF card.– Insert the CF card into the reader and connect thereader to the PC/laptop.– Start Windows Explorer and open the card reader drive.– Create a backup copy by saving the CF card files to afolder of your choice on the PC/laptop.ACTION– Format the CF card by right-clicking on the drive. Unzipthe new software that you obtained from the monito-ring service in the form of a ZIP file.