Honeywell ADEMCO VISTA-20P Series Quick Installation Manual
Also see for Ademco VISTA-15PCN: Programming guide
K5305-1QGV3 2/11 Rev. A2 Corporate Center Drive, Suite 100P.O. Box 9040, Melville, NY 11747Copyright © 2009 Honeywell International Inc.www.honeywell.com/security (A copy of the Installation and Setup Guide is available upon request)FOR DOCUMENTATION AND ONLINE SUPPORT: http://www.security.honeywell.com/hsc/resources/MyWebTech (see instructions K5305-1V9 or higher)These instructions apply to the following Honeywell security systems:ADEMCO VISTA-20P, VISTA-20PSIA, VISTA-20PCN, VISTA-15P, VISTA-15PSIA, VISTA-15PCNFeatures and procedures apply to all, except where differences are noted.VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications forFalse Alarm Reduction.Connect Devices, Zones, Sounder, and Phone Line.Refer to the Wiring Diagram on the reverse side for connection information. NOTE: This system uses a range of reserved addresses for each type of device.1. Connect keypads and other addressable devices to the ECP terminals 4-7.Refer to the wiring chart below for wire sizes and maximum wire run lengths.Wire Chart For Devices Drawing Aux Power From The Control (12V+ & 12V–)Wire TOTAL CURRENT OF ALL DEVICES CONNECTED TO A SINGLE WIRE RUNSize 50 mA or less 100 mA 300 mA 500 mA 600 mA#22 900ft (274m) 450ft (137m) 150ft (46m) 90ft (27m) 75ft (23m)#20 1400ft (427m) 700ft (213m) 240ft (73m) 140ft (43m) 120ft (37m)#18 1500ft (457m) 1100ft (335m) 350ft (107m) 220ft (67m) 170ft (52m)#16 1500ft (457m) 1500ft (457m) 550ft (168m) 350ft (107m) 270ft (82m)The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quadconductor cable is used (750 feet if shielded cable is used).Standard Keypads (6150 / 6160 series)• Keypad addresses range from address 16-23. Set each keypad’s address accordingly.NOTE: Address 16 is reserved for the first keypad and is always enabled in the control.• Use data fields ∗190-∗196 to enable keypads and set their sounding options.Expander Modules (4219, 4229)• Connect desired field wiring to the module’s zone terminals.• Expander module addresses range from 07-11. Set each module’s DIP address accordingly.• Use ∗56 Menu mode to program zone characteristics.Touchscreen Keypads (6270 / 6271 series, 8132 series; V20P = up to 4; V15P = up to 2)• Use of touchscreen keypads is independent from and in addition to the eight (8) standard keypads.• Set each touchscreen’s address accordingly (1, 2, 5, 6; see table on back) and enable in field ∗189.• Make sure the auxiliary current drain is within the control’s limitation. Otherwise use an externalpower supply to power the touchscreen keypads.RF Receiver (5881, 5883, RF Keypad)• 5881L / 5882L = up to 8 RF zones; 5881M / 5882M / 6150RF = up to 16 RF zones5881H / 5882H / 5883 / 6160RF = up to system maximum RF zones• Set the receiver’s address to 00 using the module’s DIP switches.• If using wireless keypads, set field ∗24 RF House ID Code appropriately.If receiver is mounted remotely, note the following:• Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/orblock transmissions.• Do not locate the RF receiver in an area of high RF interference (indicated by frequent orprolonged lighting of the receiver’s LED; random flicker is OK).• Do not locate RF receiver closer than 10 feet from any keypads.Relay Modules (4204)• Connect desired field wiring to the module’s relay contact terminals.• Relay module addresses range from address 12-15.Set each module’s DIP address accordingly.• Use ∗79 / ∗80 Menu modes to map each device address and define output functions.Communication Device (7847i, 7845GSM, 7845i-GSM, GSMV)• Set the communication device to address 03.• Use ∗29 Menu mode to enable and program the device.AVS System• If used, follow the installation instructions provided with the module.• Connect the AVS module to the control’s ECP terminals and connect all other ECP devices to theAVS module’s ECP terminals.• Set the AVS address using its DIP switches: V15P = 08; V20P = 11• Use the desired AVS Quick Program Command to set pre-defined options:installer code + [#] + 0 + 3: enable AVS operationinstaller code + [#] + 0 + 4: enable AVS and enable panel sounds on AVST speaker• Use field ∗55 Dynamic Signaling Priority to select the desired reporting paths.2. Connect hardwire zones to the appropriate zone terminals 8-20.3. On-Board Trigger Connections• Connect field wiring to the appropriate trigger pin using the SA4120XM-1 cable (if using 1361X10transformer) or the 4-wire cable (N4632-4, not supplied).• Trigger outputs are normally high, and go low upon programmed condition (can be set inverted).• Use ∗79/∗80 Menu modes to program the trigger outputs.• Output 17 (pin 1) = supports up to 100mA max; Output 18 (pin 5) = supports up to 20mA max4. Install Wireless Zone Transmitters.• Use ∗56 Menu mode to program wireless zones and enroll the transmitters.• Use the Go/No Go Test mode to verify adequate signal strength from each transmitter location:Enter Installer code + [#] + 4, then fault each transmitter and listen for 3 beeps at the keypad andthe zone display. Exit mode: user code + 1 (OFF).5. Connect the external sounder to terminals 3 and 4.• If supervised output desired, see Sounder Supervision wiring diagram on reverse side, and set field∗91 Option Selection for Bell Supervision.6. Connect the phone line using terminals 21-24.• Use an RJ31X jack as shown in the diagram on reverse side.Mount the Control.1. Remove the cabinet door. Remove the cabinetknockouts needed for wiring entry.2. Mount the control cabinet to a sturdy wall in aclean, dry area, which is not readily accessible tothe general public, using fasteners or anchors (notsupplied) with the four cabinet mounting holes.3. When installation and wiring is completed, installthe cabinet door and secure by using 2 screws(supplied) through the door's edge.OPTIONAL KEY LOCK: If desired, a key lock can beinstalled (K4445, not supplied). See InstallationInstructions for details.cab_6a-V0SECUREWITHSCREWS(2)Securing the Cabinet Door4. Mount the PC Board. Refer to the diagram below. If mounting an RF Receiver inside the cabinet,remove the receiver board from its case, then insert the top of the board into the slots at the top of thecabinet. Install the control board below the receiver board using the clips and screws provided. Insertgrounding lugs into the left-hand terminals of the antenna blocks and secure them with the screwsprovided. Insert the receiver's antennas into the blocks' right-hand terminals, and tighten the screws.++CIRCUITBOARDINSERT THE TOP OF THECIRCUIT BOARD INTO THESLOTS AT THE TOP OF THECABINETDETAIL BSIDE VIEWOF MOUNTING CLIPSDETAIL ASIDE VIEWOF BOARD SUPPORTINGSLOTSCIRCUITBOARDcb_mount-001-V1CABINETCABINETHANG TWO SHORT MOUNTING CLIPS(PROVIDED) ON THE RAISED CABINET TABS.SECURE THE BOARD TO THECABINET WITH THE ACCOMPANYINGSCREWSMounting the PC BoardConnect the Transformer & Battery.1321 Transformer (1321CN in Canada)• Do not plug the transformer into the AC outlet until all wiring connections to the control are complete. Asa safety precaution, always power down the control when making such connections.1361X10 Transformer(required if using Powerline Carrier devices)1. Splice one end of a 3-conductor cable to the wire ends of the SA4120XM-1 cable.2. Connect the SA4120XM-1 cable plug to the 8-pin connector on the control.3. Connect the other end of the 3-conductor cable to the 1361X10 Transformer.Canadian Installations: For Powerline Carrier Devices, use the PSC04 X-10 Interface and trigger pins.Battery Connections• After all connections to the control are completed and after AC power has been applied, connect thered and black flying leads on the control board to the battery.• IMPORTANT: This control will not power-up on battery alone (AC power must be applied). However,once the system is powered up, it will operate on battery if AC is lost.ULFor UL installations and Residential fire installations, refer to the chart below for the correct batterysize required to meet the mandatory standby time.CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE24-HOUR BATTERY BACKUP REQUIREMENTSThe California State Fire Marshal and UL have regulations which require that all residential fire alarmcontrol panels must be provided with a backup battery which has sufficient capacity to operate the paneland its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4minutes in the intended fire alarm signaling condition. This control panel can meet these requirementswithout using a supplementary power supply, provided that the panel’s auxiliary power and bell outputcurrents are limited as listed below.OUTPUT LIMITATIONS AND REQUIRED BATTERIESOUTPUT CURRENT LIMITS BATTERY INFORMATIONCurrent Total600mAmaximum total ofauxiliary powerplus bell outputcurrentsMax. Aux.Current45mA160mA200mA425mA500mABattery Capacity (Amp/Hrs)4AH7AH8AH14AH17.2AHRecommended Battery (Yuasa No.)NP4-12 (or ADEMCO 467)NP7-12NP4-12 (two) ‡NP7-12 (two) ‡NPG18-12‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries willfit inside the cabinet.)Program the Control.Refer to the Programming Guide to program the control.( The control can also be programmed via the Compass Downloader.)1. Enter Programming Mode: installer code + 8-0-0.2. Change the default Installer Code using field ∗20.3. Enter the appropriate central station phone numbers and account numbers.4. Program the system data field options as desired.4. Use the various menu modes to program zones, relay outputs, descriptors, etc.5. If AVS system is installed, use the appropriate AVS Quick Program Command.6. Program Schedules (if used): Master code + [#] + 647. Enable RF button keyfobs (if used) and assign to user numbers accordingly.8. Show the Master user how to change the default Master code:master code + [8] + 0-2 + new code + new code againTest the System.Sniffer Mode Test: To verify that all transmitters have been properly programmed, disarm all partitions.1. From a keypad in partition 1, enter Installer code + [#] + 3. All programmed transmitters are displayed.2. Fault all transmitters in turn. The display clears each transmitter as a signal is received.3. Exit Sniffer mode: Installer code + 1 (OFF). Mode does not automatically expire; you must exit manually.System Test1. Disarm the system and close all protected windows, doors, etc.2. Enter the Installer code + [5] (TEST), then press 0 = walk. (Option 1 = Dial checks phone line integrity.)3. Listen. The external sounder should sound for about 1 second then turn off.4. Fault all zones in turn and listen for three beeps from the keypad. ID of each faulted point shouldappear on the keypad display. The display clears when the zone is restored.5. Test all smoke and CO detectors following the manufacturer's instructions and check the display.6. When all zones have been checked and are intact (closed), there should be no zone identificationnumbers displayed on the keypad.7. Exit test mode: security code + [1] (OFF).Major Features and CapacitiesFeature VISTA-20P VISTA-15PPartitions 2 plus common area not partitionedZones 48 plus 16 keyfob zones fortotal of 64 zones:• 8 hardwired zones (1-8)• Up to 40 additional wiredzones (9-48) using up to 54219/4229 modules• Up to 40 wireless zones(5800 series; zones 9-48)• 4 configurable zone types32 zones plus 8 keyfob zonesfor total of 40 zones:• 6 hardwired zones (1-6)• Up to 16 additional wiredzones (9-24) using up to 24219/4229 modules• Up to 26 wireless zones(5800 series; zones 9-34)• 2 configurable zone typesSecurity Codes 48 32Schedules 32 8Keypad macros 4 2Event Logging 100 50Paging 4 2Keypads 8 8Touch Screen Devices 4 24219, 4229 5 24204 4 2Output Relays / X-10 devices 16 8On-Board Triggers 2 2Output Functions 48 24WARRANTY INFORMATIONFor the latest warranty information, please go to:www.honeywell.com/security/hsc/resources/wa |
Related manuals for Honeywell Ademco VISTA-15PCN
Honeywell ADEMCO VISTA Series Installation And Setup Manual
Honeywell ADEMCO VISTA Series Quick Manual
Honeywell ADEMCO VISTA SERIES VISTA-21iP Installation And Setup Manual
Honeywell ADEMCO VISTA 10P Installation Manual
Honeywell ADEMCO VISTA-10P Installation And Setup Manual
Honeywell ADEMCO VISTA-10P Installation And Setup Manual
Honeywell ADEMCO VISTA-40 Installation And Setup Manual
Honeywell VISTA 21iPLTE Quick Installation Manual
Honeywell ADEMCO VISTA-12A Installation And Setup Manual
Honeywell ADEMCO VISTA-48A Installation And Setup Manual
This manual is suitable for:
Product
Menu
Learn More
Menu
Legal
Menu
Copyright © 2024 OneStart. All Rights Reserved