Page 65SmartFOAMFigure 47: SmartFOAM Buttons and Indicators4. Set the foam injection rate to 1.0% by pressingthe INCR or DECR arrow buttons.5. Press the ON/OFF button to energize the HaleSmartFOAM system.a. The Pump Speed bar graph willincrease to indicate the motor isrunning.b. Observe the discharge at the bypasshose to make sure the foam pump isoperating.6. After one minute press the ON/OFF button againto stop the foam pump. Approximately onegallon (3.8 liters) of water should discharges intothe container. The TOTAL FOAM display readsapproximately 1.00.7. Exit simulated water flow. Use the stepsdescribed in step 3 and Figure 46: SettingSimulated Water Flow.8. Drain water from the foam tank and concentratelines and return the bypass valve’s handle to theINJECT position.9. Verify operation of the flow sensor. Alsocalibrate the flow sensor using the calibrationprocedures. See “User Calibration”.This completes the Hale SmartFOAM system operationchecks accomplished at the system installer facility.Foam pump feedback calibration along with setting ofuser specified default simulated flow and concentrateinjection rates should be accomplished upon delivery tothe end user using actual end user specified foamconcentrates and default values.