5-256 L60 Line Phase Comparison System GE Multilin5.6 CONTROL ELEMENTS 5 SETTINGS5The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring andsolid-state contact with voltage monitoring.5.6.8 DIGITAL COUNTERSPATH: SETTINGS CONTROL ELEMENTS DIGITAL COUNTERS COUNTER 1(8)There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions fromLogic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of anexternal contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.• COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.The units label will appear in the corresponding actual values status.• COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the casewhere a substitute relay is to be installed in place of an in-service relay, or while the counter is running.• COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic outputoperands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the setvalue.• COUNTER 1 UP: Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received whenthe accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.• COUNTER 1 DOWN: Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input isreceived when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to+2,147,483,647.• COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands areblocked. COUNTER 1COUNTER 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE COUNTER 1 NAME:Counter 1Range: 12 alphanumeric charactersMESSAGE COUNTER 1 UNITS: Range: 6 alphanumeric charactersMESSAGE COUNTER 1 PRESET:0Range: –2,147,483,648 to +2,147,483,647MESSAGE COUNTER 1 COMPARE:0Range: –2,147,483,648 to +2,147,483,647MESSAGE COUNTER 1 UP:OffRange: FlexLogic operandMESSAGE COUNTER 1 DOWN:OffRange: FlexLogic operandMESSAGE COUNTER 1 BLOCK:OffRange: FlexLogic operandMESSAGE CNT1 SET TO PRESET:OffRange: FlexLogic operandMESSAGE COUNTER 1 RESET:OffRange: FlexLogic operandMESSAGE COUNT1 FREEZE/RESET:OffRange: FlexLogic operandMESSAGE COUNT1 FREEZE/COUNT:OffRange: FlexLogic operandNOTE