5-56 L60 Line Phase Comparison System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-nates the IB signal on terminal 2 of the CT/VT module in slot F.If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces willappear.5.2.10 DATA LOGGERPATH: SETTINGS PRODUCT SETUP DATA LOGGERThe data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data maybe downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number ofchannels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-ple storage capacities for a system frequency of 60 Hz are shown in the following table. DATA LOGGERDATA LOGGER MODE:ContinuousRange: Continuous, TriggerMESSAGE DATA LOGGER TRIGGER:OffRange: FlexLogic operandMESSAGE DATA LOGGER RATE:60000 msRange: 15 to 3600000 ms in steps of 1MESSAGE DATA LOGGER CHNL 1:OffRange: Off, any FlexAnalog parameter. See Appendix A:FlexAnalog Parameters for complete list.MESSAGE DATA LOGGER CHNL 2:OffRange: Off, any FlexAnalog parameter. See Appendix A:FlexAnalog Parameters for complete list.MESSAGE DATA LOGGER CHNL 3:OffRange: Off, any FlexAnalog parameter. See Appendix A:FlexAnalog Parameters for complete list.↓MESSAGE DATA LOGGER CHNL 16:OffRange: Off, any FlexAnalog parameter. See Appendix A:FlexAnalog Parameters for complete list.MESSAGE DATA LOGGER CONFIG:0 CHNL x 0.0 DAYSRange: Not applicable - shows computed data only