Page 129Hydran* M2-X Instruction ManualMA-029 Rev. 1.0, 30-Jul-18• Parameter(s) involved:- SensTemp LL; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.- STempAlr LL (alarm set point); Temperature submenu; see Section 3.3.2.1.- TempoAlr Delay; Temperature submenu; see Section 3.3.2.1.• Alarm cause(s): Temperature of the sensor below the Alarm Lo-Lo SP alarmset pointThe sensor sensitivity is very low; repair the Hydran M2-X’s dynamic oil samplingsystem.8.1.12 S. Temp Hi Alarm• Alarm type: Due to system fault conditions.• Non-abbreviated description: High sensor temperature.• Alarm message on the Perception software: Sensor Temp High.• Priority: High.• Parameter(s) involved:- SensTemp H; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.- Alarm Hi SP (alarm set point); Temperature submenu; see Section 3.3.2.1.- TempoAlr Delay; Temperature submenu; see Section 3.3.2.1.• Alarm cause(s): Temperature of the sensor above the Alarm Hi SP alarm setpoint.Although the sensor is not affected by the temperature, monitor its temperatureregularly.8.1.13 S. Temp Low Alarm• Alarm type: Due to system fault conditions.• Non-abbreviated description: Low sensor temperature.• Alarm message on the Perception software: Sensor Temp Low.• Priority: High.• Parameter(s) involved:- SensTemp L; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.- STempAlr L (alarm set point); Temperature submenu; see Section 3.3.2.1.- TempoAlr Delay; Temperature submenu; see Section 3.3.2.1.• Alarm cause(s): Temperature of the sensor below the Alarm Low SP alarm setpoint.Although the sensor is not affected by the temperature, monitor its temperatureregularly.8.1.14 S. Tmp C. Short Alarm