5-180 F35 Multiple Feeder Protection System GE Multilin5.8 INPUTS AND OUTPUTS 5 SETTINGS5GOOSE Analogs that represent current, voltage, power, frequency, angles, or power factor can be used in a FlexEle-ment. The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz,deg, and no text (blank setting) for power factor.GOOSE Analogs can be compared to other GOOSE Analogs with any character string or no string.• GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-log™ values in other F35 features, such as FlexElements™. The base factor is applied to the GOOSE analog inputFlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 anda PU base of 0.001 is 1.When using GOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexEle-ment actual values is 2,140,000.000.The GOOSE analog input FlexAnalog™ values are available for use in other F35 functions that use FlexAnalog™ values.5.8.13 IEC 61850 GOOSE INTEGERSPATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE UINTEGERS GOOSE UINTEGER INPUT 1(16)The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-series devices. The following settings are available for each GOOSE uinteger input.• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device isoffline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integernumber.• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of theGOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.The GOOSE integer input FlexInteger™ values are available for use in other F35 functions that use FlexInteger™ values.Table 5–22: GOOSE ANALOG INPUT BASE UNITSELEMENT BASE UNITSdcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configuredunder the +IN and –IN inputs.FREQUENCY fBASE = 1 HzPHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)POWER FACTOR PF BASE = 1.00RTDs BASE = 100°CSOURCE CURRENT I BASE = maximum nominal primary RMS value of the +IN and –IN inputsSOURCE ENERGY(Positive and Negative Watthours,Positive and Negative Varhours)EBASE = 10000 MWh or MVAh, respectivelySOURCE POWER PBASE = maximum value of V BASE × IBASE for the +IN and –IN inputsSOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs GOOSE UINTEGER INPUT 1UINTEGER 1 DEFAULT:1000Range: 0 to 429496295 in steps of 1MESSAGE UINTEGER 1 DEFAULTMODE: Default ValueRange: Default Value, Last Known