GE Multilin D30 Line Distance Relay 6-216 ACTUAL VALUES 6.4 RECORDS66.4.2 EVENT RECORDSPATH: ACTUAL VALUES ÖØ RECORDS Ö EVENT RECORDSThe event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological orderfrom most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record isadded. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with theevent trigger. Refer to the COMMANDS Ø CLEAR RECORDS menu for clearing event records.6.4.3 OSCILLOGRAPHYPATH: ACTUAL VALUES ÖØ RECORDS ÖØ OSCILLOGRAPHYThis menu allows the user to view the number of triggers involved and number of oscillography traces available. The‘cycles per record’ value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillogra-phy section of Chapter 5 for further details.A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. Refer to the COMMANDS ÖØCLEAR RECORDS menu for clearing the oscillography records. EVENT RECORDSEVENT: XXXXRESET OP(PUSHBUTTON)↓MESSAGE EVENT: 3POWER ONEVENT 3DATE: 2000/07/14MESSAGE EVENT: 2POWER OFFEVENT 3TIME: 14:53:00.03405MESSAGE EVENT: 1EVENTS CLEARED Date and Time Stamps OSCILLOGRAPHYFORCE TRIGGER?NoRange: No, YesMESSAGE NUMBER OF TRIGGERS:0MESSAGE AVAILABLE RECORDS:0MESSAGE CYCLES PER RECORD:0.0MESSAGE LAST CLEARED DATE:2000/07/14 15:40:16