CHAPTER 6: ACTUAL VALUES RECORDSD30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 6-216The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in thismenu, along with the date and time stamp of the event which triggered the calculation. See the SETTINGS PRODUCTSETUP FAULT REPORTS menu for assigning the source and trigger for fault calculations. See the COMMANDS CLEARRECORDS menu for manual clearing of the fault reports and to the SETTINGS PRODUCT SETUP CLEAR RELAY RECORDSmenu for automated clearing of the fault reports.6.4.2 Event recordsACTUAL VALUES RECORDS EVENT RECORDSThe event records menu shows the contextual data associated with up to the last 1024 events, listed in chronologicalorder from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a newrecord is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associatedwith the event trigger. See the COMMANDS CLEAR RECORDS menu for clearing event records.Only major output operands generate events, not every operand. Elements that assert output per phase, for example, logoperating phase output only without asserting the common three-phase operand event.6.4.3 OscillographyACTUAL VALUES RECORDS OSCILLOGRAPHY FAULT 1 DATE:2000/08/11Range: YYYY/MM/DD FAULT 1 TIME:00:00:00.000000Range: HH:MM:SS.ssssss FAULT 1 TYPE:ABGRange: not available if the source VTs are in the“Delta” configuration FAULT 1 LOCATION00.0 kmRange: not available if the source VTs are in the“Delta” configuration FAULT 1 RECLOSESHOT: 0Range: where applicable EVENT RECORDS EVENT: XXXXRESET OP(PUSHBUTTON) Date and time stamps EVENT: 3POWER ON EVENT 3DATE: 2000/07/14 EVENT: 2POWER OFF EVENT 3TIME: 14:53:00.03405 EVENT: 1EVENTS CLEARED OSCILLOGRAPHY FORCE TRIGGER?NoRange: No, Yes NUMBER OF TRIGGERS:0 AVAILABLE RECORDS:0 CYCLES PER RECORD:0.0 LAST CLEARED DATE:2000/07/14 15:40:16