DIVAR AN 30001, 2, 3, 4, 5, 6,7, 8, 9, 10,11, 12, 13, 14,15, 16Alarm inputs: max. 16. The alarm becomes active at low voltage. Max.input voltage 15 VDC.NO1 C1,NO2 C2,NO3 C3Three groups of normal open activation outputs (on/off button).G Ground cable.DIVAR AN 50001, 2, 3, 4, 5,6, 7, 8, 9, 10,11, 12, 13, 14,15, 16Alarm inputs: max. 16. The alarm becomes active at low voltage.NO1 C1,NO2 C2,NO3 C3,NO4 C4,NO5 C5Groups of normal open activation alarm outputs (on/off button).CTRL +12V Control power output. Always close the device power to cancel thealarm.+12V External power output. Need the peripheral equipment to provide+12 V power (below 500 mA).G Ground cable.Connecting the alarm inputEach (alarm) input line can be switched by a contact from an external device between anumbered input and ground (G). Wire the inputs as either Normally Open (NO) or NormallyClosed (NC) and configure them as NO or NC in the system menu (Settings > Alarm). Thedefault is NO.See the following guidelines:– Parallel connect the COM end and GND end of the alarm detector (provide externalpower to the alarm detector)– Parallel connect the DVR ground and the alarm detector ground– Connect the NC port of the alarm sensor to the DVR alarm input (ALARM)– Use the same ground as the DVR if external power is used for the alarm device– When connecting two DVRs (or one DVR and one other device), use a relay to separatethem5.10.134 en | Hardware setup DIVAR AN 3000 / DIVAR AN 50002015.10 | v2.3 | AM18-Q0669 Operations Manual Bosch Security Systems