The connecting piece supplied with your WTA 3510dryer must then be inserted in the vent opening that willbe used. See Figure 16.Figure 16. The ducting system of the dryer, for optimumperformance, should be as short as possible witha minimum number of elbows. Your WTA 3510 electricvented dryer will work best when the venting system hasas few restrictions to the flow of air as possible.Whether installing to an existing venting system or a newventing system, make sure that all ducting is clean andfree of lint and does not exceed the length per elbows asshown in Table 1, below:Maximum length of ductNumberof ElbowsRigid Duct Flexible Duct012330 ft. (914 cm)22 ft. (670 cm)14 ft. (427 cm)6 ft. (183 cm)20 ft. (610 cm)15 ft. (457 cm)9 ft. (274 cm)4 ft. (122 cm)Table 1.Every elbow must have a minimum diameter of 4 inches(10 cm).The above table assumes the use of an approvedexhaust vent hood with a swing out damper. DO NOTuse an exhaust vent hood with magnetic latches.To avoid restriction of exhaust the outlet must bea minimum of 12 inches (30 cm) above ground level, orany other obstructing surface, as shown below, inFigure 17.12” (30 cm) min.Figure 17.Step 5Condensate Hose Connection(Model WTL 5410 only!)The WTL 5410 must have its condensate drain lineinstalled and run to a suitable drain. The connectionfor the condensate hose is located on the back of theWTL 5410, see Figure 18.Figure 18.Connect the condensate drain hose to the dryer.The other end should then be placed and secured ata nearby sink or drain, or if installed with a washer itmay, room permitting, be installed next to the washerdrain hose and drained to the same drain used by thewasher.Be sure to follow all local codes and regulations inrunning the condensate to a suitable drain.