Manual 2100-587BPage 6 of 59AIR CONDITIONING MODULE OPTIONSSTD = Standard equipment.1 CCM Compressor control module has adjustable 30 second to 5 minute delay-on-breaktimer. On initial power up, or any time the power is interrupted, the delay-on-makewill be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockoutfeature (with 1 retry) for high and/or low pressure controls, and a 2 minute timedbypass for low pressure control.2 HPC High pressure control is auto reset. Always used with compressor control module(CCM) which is included. See note 1.3 LPC Low pressure control is auto reset. Always used with compressor control module(CCM) which is included. See note 1.4 LAC Low ambient control permits cooling operation down to 0°F.1MCC2CPH3CPL4CALdellatsnIyrotcaFedoCdellatsnIdleiFtraPDTS DTS DTS X A/NDTS DTS DTS H 82-AMCCAUTIONDuring the initial firing of the burners there will probably be some amount of smoke issued to thecirculating air stream as the result of residual oil burning off of the heat exchanger tubes. This oilis required during the forming process of the stainless steel heat exchanger tubes to facilitate thebending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. Invapor form this may be irritating to the eyes or could cause headaches. This is a one-timeoccurrence, and ventilation of the space may be required depending upon the space beingconditioned.