INSTALLATIONMOUNTING THE STATION HOUSING3 - 16 I-E96-117B®2. Connect the successive stations (maximum of 8, 4 from P2,4 from P3) to the first station using a KCS (only 1 analog inputwith KDS), NKDS02 or NKDS12 cable. There is an additionalconnector on the KCS or KDS that connects to the NKDS03and NKDS13 cable. Figure 3-4 shows a diagram of an intercon-nected installation.NOTE: Only the first interconnected SAC station can bypass ananalog output. The first interconnected SAC station connected to P2of the TCS termination unit bypasses analog output number 1. Thefirst interconnected SAC station connected to P3 of the TCS termi-nation unit bypasses analog output number 2.Cable Connections for the NTRL03 Termination UnitFigure 3-5 shows the cable connections for the NTRL03 termi-nation unit. For more information refer to the NTRL02 andNTRL03 Fiber Optic Remote Link and Electrical RemoteLink Termination Units product instruction.Cable Connections for the NIRL03 Termination ModuleFigure 3-6 shows the cable connections for the NIRL03 termi-nation module. For more information refer to the NIRL03Remote Link Termination Module product instruction.Figure 3-3. Cable Connections for Two Analog Control Stations on One TCS Termination UnitIMCIS02IMMFP01/02/03P1P1P3P3P2P2NKTU01/11NKTU01/11NKTU01/11NKSE01/11T00298ANKSE01/11NKSE01/11NKDS01/11NKCS01/11NKDS01/11NKCS01/11TOREDUNDANTMFP TO SECONDGROUP OF UPTO 32 STATIONSTO ADDITIONAL NTCS04AS REQUIRED(32 STATIONS MAX)P2P2P3P1P1P7P5P5P4P6P4P3NTMP01NTCS04IISAC01(WITH BYPASS)IISAC01(WITH BYPASS)P1P1