ADDITIONAL SCALING PAOAMETEOSOTEE:N The programming instructions below are only available for loop powered units Battery powered units do not includethese programming parametersFlow 4 mA SettingZero is the default flow rate at the 4 mA setting If the current selection is correct, press ENTEO to advance to the Flow 20 mAparameter To change the setting, press UP to increment the flashing digit and press OIGHT to move to the next digit PressENTEO to save and advance to the Flow 20 mA parameterFlow 20 mA SettingThe turbine meter’s maximum flow rate is the default value for the 20 mA setting If the current selection is correct, pressENTEO to advance to the 4…20 mA Calibration parameter To change the setting, press UP to increment the flashing digit andpress OIGHT to move to the next digit Press ENTEO to save and advance to the 4…20 mA Calibration parameter4…20 mA CalibrationThe 4…20 mA Calibration parameter is the fine adjustment of the 4…20 mA output The 4 mA setting is typically between35…50 To set the 4 mA value, connect an ammeter in series with the loop power supply At the 4MA OUT prompt, press UP toincrement and OIGHT to decrement the 4 mA value to until a steady 4 mA reading is reached on the ammeter Press ENTEO tolock in this value and advance to 20MA OUT The 20 mA adjustment is performed using the same procedure as the4 mA adjustment4…20 mA TestThe monitor contains a diagnostic routine that allows the simulation of mA values between 4…20 to check output trackingAt the 4-20TEST prompt press UP to increment the simulated mA output or OIGHT to decrement the value in increments of1 mA The ammeter should track the simulated mA output If a 4…20 mA test in not necessary, press ENTEO once to escapethe testing at any timePulse Out Freq. In4-20 mA10…30V DC1…5V DC1 2 3 4 5 6+ - + - + -JP2MagInputPulseInuputTB11 2 3 4 5J2KeypadConnectorDCPULSE OUTPUTIO/SETUPDSPFlow 4MAFlow 20MA4MA OUT20MA OUT4-20 TESTPASSWORDFigure 4: Typical ammeter connection Figure 5: 4…20 mA programming menuAdditional Scaling ParametersPage 8 November 2017DSY-PM-00278-EN-04