Steca XtenderInstallation and Operating Instructions 723.932 Xtender V0.511 Seite 3715 Technical dataModel XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH 8000-48InverterRated battery voltage 12 V 24 V 48 V 48 VInput voltage range 9.5 - 17 V 19 - 34 V 38 - 68 V 39 - 68 VContinuous power @ 25 °C 2,500 VA 4,000 VA 5,000 VA 7,000 VASmart boost power 2,500 VA 4,000 VA 5,000 VA 7,000 VA30 minute charge @ 25 °C 3,000 VA 5,000 VA 6,000 VA 8,000 VA5 second charge @ 25 °C 3 x PnomMaximum charge Up to short-circuitMaximum asymmetrical charge Up to PnomLoad detection (standby) 2 to 25 WAdmissible cos phi 0.1 – 1Maximum efficiency 93% 94% 96% 96%Open-circuit powerOFF/standby/ON1.7 W/2.2 W/14W1.8 W/2.5 W/20W2.2 W/3 W/22 W 2.2 W/3.8 W/34WOutput voltage 230 Vac (-10% /0)Output frequency 50/45-65 Hz +/- 0.05% (quartz-controlled)Harmonic distortion <2%Dynamic correction 0.5 ms (charge leap from 0 to 100%)Overcharge and short-circuit Automatic disconnection then 2 startup attemptsOverheating protection Alarm prior to disconnection and automatic restartBattery charger6-phase battery charger Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)Adjustable charge current 0 - 160 A 0 - 140 A 0 - 100 A 0 - 120 AInput current sharing system 1 - 30 A 1 - 50 AMaximum input voltage 265 VacAC input voltage range Level of detection adjustable from 150 to 230 VacAdmissible input frequency 45 - 65 Hz(PFC) EN 61000-3-2Battery control (factory value / adjustable range with RCC-02)End of absorption by duration 4 / 0.25 - 10 h or by current - / 4 - 30 AAbsorption voltage 14.4 / 9.5 - 18 V 28.8 / 19 - 36 V 57.6 / 38 - 72 VPeriodic absorption voltage - / 9.5 - 18 V - / 19 - 36 V - / 38 - 72 VMaintenance voltage 13.6 / 9.5 - 18 V 27.2 / 19 - 36 V 54.4 / 38 - 72 VReduced maintenance voltage - / 9.5 - 18 V - / 19 - 36 V -- / 38 - 72 VEqualisationEnd of equalisationEqualisation voltage - / 9.5 - 18 V - / 19 - 36 V - / 38 - 72 V10.8 / 9.5 - 18 V 21.6 / 19 - 36 V 43.2 / 38 - 72 V- / 0 - 32 days- / 0 - 10 hoursTemperature compensation -5 / 0 to-8 mV/°C/cell (optional BTC-01)General dataAuxiliary contacts 2 independent contacts 16 A - 250 Vac (potential-free 3 points)Maximum transfer relay current 30 A 50 AMaximum transfer time <25 msWeight 34 kg 40 kg 42 kg 46 kgDimensions: H x W x D [mm] 220x290x500 220x310x500Protection degree IP23Conformity EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,Dir. 89/336/EEC, LVD 73/23/EECOperating temperature range -20 to 55 °CVentilation Forced from 45 °CNoise level <35 dB / <50 dB (without / with ventilation)Warranty 2 yearsOptionsBattery temperature sensor : BTS-01Remote control and programming centre: RCC-02 / RCC-03