23Charts and DrawingsTable 8 - EQ Air Cooled Chiller Electrical SpecificationsModel Voltage Compressor Pump Condenser Fan Control Circuit Unit MCA2RLA1 Power (HP) FLA Power (HP) FLA FLAEQ3A01 208/1/60 5.9 ¼ (.186 kW) 2.7 1/4 (.186 kW) 1.7 0.24 12.8230/1/60 5.4 2.4 1.6 0.22 11.8EQ2A02208/3/60 9.51 (.745 kW)3.91/4 (.186 kW)(single phase)1.7 0.24 18.5230/3/60 8.6 3.6 1.6 0.22 17.0460/3/60 4.3 1.8 0.8 0.11 9.0208/3/60 9.52 (1.49 kW)7.5 1.7 0.24 22.1230/3/60 8.6 6.8 1.6 0.22 20.2460/3/60 4.3 3.4 0.8 0.11 10.6208/3/60 9.53 (2.24 kW)10.6 1.7 0.24 25.2230/3/60 8.6 9.6 1.6 0.22 23.0460/3/60 4.3 4.8 0.8 0.11 12.0208/3/60 9.5 2 (1.49 kW)2-stg8.8 1.7 0.24 23.4230/3/60 8.6 8.0 1.6 0.22 21.4460/3/60 4.3 3.7 0.8 0.11 10.9EQ2A03208/3/60 12.61 (.745 kW)3.9½ (.372 kW)(single phase)3.0 0.24 23.6230/3/60 11.4 3.6 2.9 0.22 21.5460/3/60 6.2 1.8 1.5 0.11 11.9208/3/60 12.62 (1.49 kW)7.5 3.0 0.24 27.3230/3/60 11.4 6.8 2.9 0.22 25.0460/3/60 6.2 3.4 1.5 0.11 13.7208/3/60 12.63 (2.24 kW)10.6 3.0 0.24 30.4230/3/60 11.4 9.6 2.9 0.22 27.8460/3/60 6.2 4.8 1.5 0.11 15.1208/3/60 12.6 2 (1.49 kW)2-stg8.8 3.0 0.24 28.6230/3/60 11.4 8.0 2.9 0.22 26.2460/3/60 6.2 3.7 1.5 0.11 14.0Notes:RLA (Rated Load Amps) based on a percentage of the MMTC (Maximum Must Trip Current) as established by the manufacturer in accordance with ULStandard 465.MCA (Minimum Circuit Ampacity) based on 125% of the compressor RLA plus 100% of remaining components FLA in accordance with NEC 440-33. MCAshown also include 1 amp value for the control circuit.Voltage Utilization range is: 208 (187 to 229), 230 (187 to 254), and 460 (414 to 506).