3 BASIC CONFIGURATION LEVEL…3.3 Set Up ChartInformation.• Programmable chart duration – between 1 and 167 hours or 7 and 32 days.• Chart stop function – the chart can be stopped by an alarm, digital input, logic equation result or a real time event (if timeroption is fitted).• Auto pen drop – automatically drops the pen(s) onto the chart after a 5 minute delay to ensure recording is not left disabledinadvertently.Page Header – Set Up ChartTo advance to Set Up Alarms Page press the switch.Chart DurationSelect the chart duration required per revolution of the chart; between 1 and 167 hours or 7 and32 days.Stop Chart SourceSelect the source required for stopping the chart.For a description of sources – see Table 3.1 on page 15.Auto Pen DropSelect 'YES' to enable or 'NO' to disable.If 'YES' selected, pen(s) drop automatically onto the chart 5 minutes after they are lifted.If 'NO' selected, the pen(s) remain lifted until they are manually dropped by the operator.Pen Lift Enable/DisableThe switch can be disabled if required. Select 'YES' to enable or 'NO' to disable.Pen Lift/Pen StatusTo raise pen(s) press switch. The following status displays are shown:rECOrd – pen records on chartLIFt – pen lifts off chartPArK – pen moves to park positionAt rEF – pen at reference positionTo lower pen(s) press switch. The following status displays are shown:rEtUrN – pen returns to record positiondrOP – drops (lowers) onto chartrECOrd – pen records on chartReturn to top of Set Up Chart Page.SEt UPCHArtCHArtCH–StP32dY1HrPENLFtEQN–4NONErECOrdLFt EN–––AUtdrP–––LIFtPArKAt rEFdrOPrEtUrNSEt UPCHArt