43PID Controller----Control Action----Prop. Band% Man100.0Output TypeIntegral TimeSecs100Derivative TimeSecs10.0----Controllerset to PIDRev.DirectPulseAnalogTimePower RecoveryPulses/MinuteCycle TimeOutput RangeSee Section 5.8.2.Control ActionSet the required control action:Rev. – Reverse acting – see Appendix B, Fig. B2.Direct – Direct acting – see Appendix B, Fig. B3.Proportional BandSet the required proportional band, between 0.0 and 999.9% in 0.1% increments.Integral Action TimeSet the integral action time, between 1 and 7200 seconds in 1 second increments.Set to OFF to disable integral action time.Derivative Action TimeSet the derivative action time, between 0.1 and 999.9 seconds in 0.1 second increments.Set to OFF to disable derivative action time.Output TypeSet the required output type:Time – Time proportioning (relay 1)Analog – Analog output (analog output 1)Pulse – Pulse frequency (relay 1)Output Type set to Time – continued on next page.Output Type set to Analog – continued on next page.Output Type set to Pulse – continued on page 45.…5.8 Configure Control5.8.1 Configure Single PID Controller5 PROGRAMMING…