Fault tracing 317Alarms generated by the Basic control panelThe Basic control panel indicates control panel alarms with a code, A5xxx.ALARM CODE CAUSE WHAT TO DO5001 Drive is not responding. Check panel connection.5002 Incompatiblecommunication profile Contact your local ABB representative.5010 Corrupted panel parameterbackup file Retry parameter upload.Retry parameter download.5011 Drive is controlled fromanother source. Change drive control to the local control mode.5012 Direction of rotation islocked. Enable change of direction. See parameter1003 DIRECTION.5013 Panel control is disabledbecause start inhibit isactive.Start from the panel is not possible. Reset theemergency stop command or remove the 3-wirestop command before starting from the panel.See section 3-wire macro on page 105 andparameters 1001 EXT1 COMMANDS, 1002EXT2 COMMANDS and 2109 EMERG STOPSEL.5014 Panel control is disabledbecause of drive fault. Reset drive fault and retry.5015 Panel control is disabledbecause the local controlmode lock is active.Deactivate the local control mode lock and retry.See parameter 1606 LOCAL LOCK.5018 Parameter default value isnot found. Contact your local ABB representative.5019 Writing non-zeroparameter value isprohibited.Only parameter reset is allowed.5020 Parameter or parametergroup does not exist orparameter value isinconsistent.Contact your local ABB representative.5021 Parameter or parametergroup is hidden. Contact your local ABB representative.5022 Parameter is writeprotected.Parameter value is read-only and cannot bechanged.5023 Parameter change is notallowed, when drive isrunning.Stop drive and change parameter value.5024 Drive is executing a task. Wait until task is completed.5025 Software is being uploadedor downloaded.Wait until upload/download is complete.5026 Value is at or belowminimum limit.Contact your local ABB representative.5027 Value is at or abovemaximum limit.Contact your local ABB representative.5028 Invalid value Contact your local ABB representative.