ACQ550-U1 User’s Manual 67Application macrosMacro default values for parametersParameter default values are listed in section Complete parameter list on page 69.Changing from the default macro (ABB Standard), that is, editing the value ofparameter 9902, changes the parameter default values as defined in the followingtables.Note: Configured for 60 Hz/NEMA compliance (ACQ550-U1).ACQ550-U1Parameter ABB 2-wire 3-wire AlternateMotorPotentio-meterHand-auto PID Control PFC Control9902 APPLIC MACRO 1 =ABB STANDARD2 =3-WIRE3 =ALTERNATE4 =MOTOR POT5 =HAND/AUTO6 =PID CONTROL7 =PFC CONTROL9904 MOTOR CTRL MODE 3 = SCALAR:FREQ1 = VECTOR :SPEED1 = VECTOR :SPEED1 = VECTOR :SPEED1 = VECTOR :SPEED1 = VECTOR :SPEED3 = SCALAR :FREQ1001 EXT1 COMMANDS 2 = DI1,2 4 = DI1P,2P,3 9 = DI 1F ,2R 2 = DI 1,2 2 = DI 1,2 1 = DI1 1 = DI11002 EXT2 COMMANDS 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 7 = DI6,5 6 = DI6 6 = DI61003 DIRECTION 3 = REQUEST 3 = REQUEST 3 = REQUEST 3 = REQUEST 3 = REQUEST 1 = FORWARD 1 = FORWARD1102 EXT1/ EXT2 SEL 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 3 = DI 3 2 = DI 2 3 = DI 31103 REF 1 SELECT 1 = AI1 1 = AI1 1 = AI1 12 =DI 3U ,4D ( NC ) 1 = AI1 1 = AI1 1 = AI11106 REF 2 SELECT 2 = AI2 2 = AI2 2 = AI2 2 = AI2 2 = AI2 19 = PID1OUT 19 = PID1OUT1201 CONST SPEED SEL 9 = DI3,4 10 = DI4,5 9 = DI 3,4 5 = DI 5 0 = NOT SEL 9 = DI 3,4 0 = NOT SEL1304 MINIMUM AI2 0.0% 0.0% 0.0% 0.0% 20.0% 20.0% 20.0%1401 RELAY OUTPUT 1 1 = READY 1 = READY 1 = READY 1 = READY 1 = READY 1 = READY 2 = RUN1402 RELAY OUTPUT 2 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 3 = FAULT(-1)1403 RELAY OUTPUT 3 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 3 = FAULT(-1) 31 = PFC1501 AO1 CONTENT SEL 103 = 0103OUTPUT FREQ102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED103 = 0103OUTPUT FREQ1507 AO2 CONTENT SEL 104 =CURRENT104 =CURRENT104 =CURRENT104 =CURRENT104 =CURRENT104 =CURRENT130 =PID 1 FBK1510 MINIMUM AO2 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 4.0 mA1601 RUN ENABLE 0 = NOT SEL 0 = NOT SEL 6 = DI 6 6 = DI 6 4 = DI 4 5 = DI 5 2 = DI 22201 ACC / DEC 1/2 SEL 5 = DI5 0 = NOT SEL 5 = DI 5 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL3201 SUPERV 1 PARAM 103 = 0103OUTPUT FREQ102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED103 = 0103OUTPUT FREQ3401 SIGNAL 1 PARAM 103 = 0103OUTPUT FREQ102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED102 = 0102SPEED103 = 0103OUTPUT FREQ4001 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.54002 INTEGRATION TIME 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s4101 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.54102 INTEGRATION TIME 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s8123 PFC ENABLE 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 1 = ACTIVE