VCCX2 Controller Technical GuideVCCX2 CONTROLLER WIRING29Return Air Temperature Sensor WiringReturn Air Temperature SensorThe R36340 (6 inch) or P87140 (12 inch) Return Air TemperatureSensor must be wired as shown for proper operation. The Return AirTemperature Sensor is a 10K Type III thermistor sensor. The ReturnAir Temperature Sensor should be mounted in the return air duct. Ifthe system has a Zoning Bypass Damper installed, be sure the returnair sensor is located upstream of the bypass duct connection. SeeFigure 13, below for details.Figure 13: Return Air Temperature Sensor Wiring