PAGE 74. APPROVALSETH-NODE1V46CAI Approvals InformationCSAClass II, Division 2, Groups F and G T130°CTamb: -20°C to +50°CATEXBaseefa11ATEX 0033XEx II 3D Ex tc IIIC T125°Dc IP66TAMB -20°C to +45°CIECExIECEx BAS11.0018XEx tc IIIC T125°Dc IP66TAMB -20°C to +45°CETH-NODE1V4CAI Approvals InformationCSAClass II, Division 2, Groups F and G T130°CTamb: -20°C to +50°CATEXBaseefa04ATEX0131XEx II 2D Ex tb IIIC T125° Db IP66TAMB -20°C to +50°CIECExIECEx BAS05.0026XEx tb IIIC T125° Db IP66TAMB -20°C to +50°CSPECIAL CONDITIONS OF USE• The equipment shall be suitably earth bonded via the PCB mounted earth terminal inside theequipment enclosure.• Warning: The equipment is a potential static hazard, clean only with a damp cloth.• Do not allow dust layers to build up on the equipment.