14Indoor CS-PC28QKH (Others/S. E. ASIA)Model Outdoor CU-PC28QKH (Others/S. E. ASIA)Height(I/D / O/D) mm (inch) 290 (11-7/16) / 750 (29-17/32)Width (I/D / O/D) mm (inch) 1070 (42-5/32) / 875 (34-15/32)DimensionDepth (I/D / O/D) mm (inch) 240 (9-15/32) / 345 (13-19/32)Weight Net (I/D / O/D) kg (lb) 12 (26) / 62 (137)Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 15.88 (5/8)Standard length m (ft) 5.0 (16.4)Length range (min – max) m (ft) 3 (9.8) ~ 30 (98.4)I/D & O/D Height different m (ft) 20 (65.6)Additional Gas Amount g/m (oz/ft) 30 (0.3)PipingLength for Additional Gas m (ft) 7.5 (24.6)Inner Diameter mm 12Drain Hose Length mm 550Fin Material Aluminium (Pre coated)Fin Type Slit FinRow x Stage x FPI 2 x 15 x 21Indoor HeatExchangerSize (W x H x L) mm 810 x 315 x 25.4Fin Material Aluminium (Blue coated)Fin Type Corrugate FinRow x Stage x FPI 2 x 28 x 19OutdoorHeatExchangerSize (W x H x L) mm 44 x 711.2 x 836.9Material PolypropeleneAir Filter Type One-touchPower Supply OutdoorPower Supply Cord A 20Thermostat MechanicalProtection Device -DRY BULB WET BULBMaximum °C 32 23Indoor Operation Range Minimum °C 16 11Maximum °C 43 26Outdoor Operation Range Minimum °C 16 111. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor airtemperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb).2. Specifications are subjected to change without prior notice for further improvement.