5. For SG800VA - SG1kVA and 208-240V models, connect the power cord to the UPSinlet located on the UPS rear panel. On SG1.5K - SG3K 120V models the line cord ispermanently attached to the UPS.6. Select a suitable location for the UPS, near enough to the computer or equipment toto be protected. Connect the power cord(s) for the equipment to be protected to theUPS output receptacles.VERIFY THE TABLE OR SURFACE SUPPORTING THE UPS WILL SUPPORT THEWEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.800VA-1KVA UPS MODELS = 33 lbs. (14.9 kg)1.5KVA- 2KVA UPS MODELS = 68.4 lbs. (31 kg)3KVA UPS MODELS = 81.4 lbs. (37 kg)2 & 3kVA-1TX, -1TXI, -2TX & -2TXI models = 150 lbs. (68 kg)MINI-TOWER EXTENDED BATTERY BANKS = 123 lbs. (55.8 kg) MAX. (EACH BANK)FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)7. If extended battery banks are to be connected to the UPS, please refer to page 8 forfurther instructions.8. If unattended computer shutdown and monitoring are desired, connect the greenUPS/Computer cable to the DB-9 connector located on the UPS rear panel. Theninstall the shutdown and monitoring software provided with the UPS. For yourreference, UNIX shutdown and monitoring software is available from Falcon Electricat an additional cost.9. Verify the location selected has adequate ventilation to allow for the proper cooling ofthe UPS.DO NOT BLOCK UPS FANS OR AIR VENTS. THE UPS MUST NOT BEINSTALLED IN AN ENCLOSED AREA.10. Plug the UPS power cord into the nearest grounded wall outlet. SG1K-2T 208-240Vmodels will automatically turn on since they do not have an input circuit breaker. Forall other SG models, go to step 12.11. Turn the input circuit breaker located on the UPS rear panel to the “on” position. Theinternal UPS fan and front panel "line" indicator should turn on, followed by the"bypass" LED, and after several seconds, the "inverter" LED.12. Turn on the connected equipment and verify the UPS does not go into overload byobserving the front panel load indicator LEDs.13. The UPS, optional external battery bank(s) and additional chargers should be pluggedin and turned on for 24 hours to charge the batteries. During this initial 24 hourcharging period, battery backup time may be substantially reduced.TO TURN OFF THE UPS, SWITCH OFF THE INPUT CIRCUIT BREAKERLOCATED ON THE UPS REAR PANEL AND PRESS THE ON/OFFBUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS.THE UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUTDOWN. DO NOTPRESS THE ON/OFF BUTTON OR TURN THE CIRCUIT BREAKER ON AGAINDURING THE SHUTDOWN PROCESS OR THE UPS WILL GO TO AN ALARMCONDITION, WARNING THAT THE UPS WAS NOT SHUTDOWN PROPERLY.SHOULD THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN ANDWAIT UNTIL THE UPS SHUTS DOWN.IMPORTANT5